Study on isolation effects of isolation wards (2)

Xu Zhonglin, Zhang Yizhao, Wang Qingqin, Wen Feng, Liu Hua, Zhao Li, Feng Xin, Zhang Yanguo, Wang Rong, Niu Weile, Di Yanqiang, Yao Dan, Yu Xihua, Yi Xinwen, Ou Yanchuan, Lu Weiming

2015.02.03

Analyses the cognition to pressure difference function and the pressure difference values recommended in foreign literatures. Experimentally studies the relation of the pressure difference and leakage rate of contaminations separately by atmospheric dust method and experimental culture method. The results show that the leakage concentration ratio of contaminations decreases about 0.03 when the pressure difference changes from 0 to -6 Pa and that the leakage concentration ratio almost keep the same value when the pressure difference changes from -6 Pa to -30 Pa. Recommends the pressure difference value of -5 Pa.