Performance comparison of multicoupled air conditioning units with single compressor and double compressor
Jiang Yantao, Yang Changzhi, Tian Mingli, He Li
2015.02.03
Compares the energy efficiency ratio (EER) and integrated part load value (IPLV) of multicoupled air conditioning units with a single frequency conversion compressor and a double compressor system with a joint of a frequency fixed compressor and a frequency conversion compressor by experiments. The results indicate that the average EER and IPLV of the double compressor system are 36 W/W and 367 respectively, while those of the single compressor system are 31 W/W and 321 respectively, which proves that the double compressor frequency conversion air conditioning unit has better energy efficiency.