Simulation of energy consumption of air conditioning system for an office building
Wang Rong, Wang Yi, Jin Xiaogong, Lü Fang, Han Xu and Zhu Peigen
2015.02.02
Simulates and calculates the annual hourly cooling and heating load of each zone and the energy consumption of the air conditioning system with DeST software, and analyses the influence of different area ratios of window to wall and shading elements on energy consumption. Determines the appropriate area ratio of window to wall in south exposure of 0.34. The cladding stone shading element can reduce the annual accumulated cooling load index by about 2.18 percent.