Annual energy consumption analysis for an underground railway station with temperature and humidity independent processed air conditioning system in Qingdao
Hou Xikuai, Liu Yijiang, Li Junfei
2014.12.15
Calculates the air conditioning cooling load based on the local annual meteorological data, and compares the annual energy consumption under hourly loads between ordinary air conditioning systems and the temperature and humidity independent processed air conditioning system (THIC). The result shows that the annual energy consumption of THIC is about 26.2% lower than that of an ordinary air-conditioning system, and it has better application prospects in the underground railway stations.