Technical indexes of water-cooled chiller condenser tube automatic on-line cleaning device with rubber balls
Ni Yonggang, Liu Jinping, Zhang Yajun, Wang Haipeng,Zhang Yongkang, Tan Weixiang, Liu Wenfei and Liu Xuefeng
2015.01.29
Presents the application status and operation principle of the device. It is put forward using the approaching temperature for describing the fouling resistance for the condenser in the standard of Chiller condenser tube automatic on-line rubber ball cleaning equipment. The approaching temperature rise should be no greater than 0.3 ℃ with a deviation of 0.1 ℃, and represents the calculation method of approaching temperature rise on partial load conditions.