Air conditioning cooling load calculation method and comparison and improvement of calculation software

Sun Deyu, Xu Wei, Zou Yu and Chen Xi

2015.01.29

Considering the marked differences in calculation results by existed calculation software, compares and analyses the calculation results of 43 examples by a program comparison and verification method. For the models of different software, there are notable variances in the convection share and radiation share for different heat gain types, and the distribution models of radiation heat between the inner surfaces; and the correction factors are different. The software mainly adopt the harmonic response method and the cooling load coefficient method, of which the theoretical calculation result of heat gain are approximately identical while the cooling load calculation result are different. Improves the calculation precision and accuracy by substituting the convection and radiation proportions of heat gain from the latest international research findings for the original data and improving the distribution model of radiation heat between the inner surfaces. As a result, the calculation deviation of different software can be reduced to less than 10% by improving the calculation method.