Problems in conventional measuring method of air changes and its improvement
Jiang Xuan, Shao Xiaoliang, Li Xianting and Zhou Bin
2015.01.28
By means of field measurement and numerical simulation analyses, taking a tracer gas dropping technique as an example, points out the problems existing in conventional measuring method with tracer gases that the differences among different points cannot be reflected correctly as the measured air changes of different points are almost the same when using the fitting curve slope of concentration according to the uniform mixture theory. Meanwhile, in the method of solving the average room air changes exists some deficiency in mathematical fundaments. Proposes adopting the index reflecting local air change ability—air changes of local area. Gives a procedure for solving the new index.