Characteristics of air flow and sound wave through ventilation windows

Lei Junyong, Li Hui and Li Junming

2015.01.28

Based on the aerodynamical noise theory, establishes a physical model, and simulates and analyses the noise sound power level distribution of the window and indoor space at different velocities of air flow through cracks around the window.The results show that for a typical window, the aerodynamical noise can be neglected if the air velocity is less than 5 m/s; when the air velocity is larger than 20 m/s, the noise source larger than 60 dB would appear in the jet separation zone, and the noise source larger than 40 dB would appear in broader downstream zone; when the air velocity is larger than 30 m/s, the noise larger than 60 dB would appear in broader downstream zone, and local noise approaches 80 dB; the retrofit to the windows structure will decrease this aerodynamical noise.