Outdoor climate distribution of thousand-meter buildings and its effect on building heating and cooling loads

Cao Junliang, Liu Jing, Man Xiaoxin, Li Yue, Jiang Yongming and Li Zhuangzhuang

2015.01.20

Based on the outdoor climate condition in Dalian, simulates the vibration of outdoor air temperature, relative humidity and wind speed with the height using the mesoscale weather research and forecasting model WRF V3.4. The results indicate that the outdoor air temperature and relative humidity varies linearly within the range of 0 to 1 000 meters, and the temperature decreases about 0.6 ℃ and the relative humidity increases about 2% with the height increasing 100 meters. The wind speed increases exponentially below 500 meters and varies little above 500 meters, the heat transfer coefficient of building envelope increases 3.3% at maximum within the range of 0 to 1 000 meters, and the influence of wind speed can be considered by simply verification or be ignored in calculating air conditioning load.