Dust particle characteristics in general office environment

Fan Yuesheng, Li Angui and Si Pengfei

2015.01.12

Experimentally studies the distribution characteristics of the indoor dust particles and the ratio of the indoor to outdoor particle concentrations (I/O). The results indicate that the indoor and outdoor particles are mainly smaller particles, with those of 1.0 to 3.0 μm in diameter accounting for 46.70% and 45.06% of the TSP of indoor and outdoor respectively; the I/O value of TSP is in the range of 0.61 to 0.72, and the I/O value of PM10 is in the range of 0.64 to 0.74; the I/O value reduces with the increase of the diameter and is in the range of 0.406 to 0.995, and the variation trend is that the I/O value drops sharply with smaller diameter and then appears a gentle decline, which is different from that on natural ventilation conditions.