Testing and analysis of heat transfer properties of sewage heat exchangers
Wu Zi,Zhang Shigang,Fu Lin, Yuan Weixing
2015.01.12
Taking the sewage heat exchanger of a hotel in Beijing as study object, continuously tests the variation in flow rate and temperature of sewage, intermediate water and hot water with time. Based on the tested data, obtains the decaying condition of the heat exchanger efficiency with the using time due to scale formation,and obtains a fitted decaying formula of the heat transfer coefficient. The analysis results provide a reference for the design and selection of sewage heat exchanger of a sewage source heat pump.