Study of maximum heating radius of seawater-source heat pump district heating systems
Shu Haiwen, Duanmu Lin, Zhu Yingxin
2015.01.07
On the basis of the ratio of electricity consumption to transferred heat quantity (EHR) propagated in the national building energy efficiency design standard, obtains the index of primary energy consumption ratio of hot water transportation to the heat supplied (EHR′). Calculates the maximum heating radiuses of seawater-source heat pump district heating systems (SSHPDHS) under different indexes of EHR′. The calculation results show that if the indexes of EHR′ are set at 5%, 10%, 15% and 20%, the maximum district heating radiuses of SSHPDHS with supply and return hot water temperature difference of 10 ℃ are 0.875, 2.75, 4.625 and 6.5 km respectively.