Transportation of indoor airborne pollutant with a coupled ventilation system

Wang Haihua, Liu Di, Tang Guangfa

2015.01.05

Analyses the effect of a window-type air conditioner on the progress with the CFD. Establishes the Reynolds stress model (RSM) to describe the indoor air flow and contaminant transportation. Illustrates the effect of supply air velocity, fresh air ratio, cleaning efficiency and heat source intensity on the airborne pollutant transportation. The results show that the reduction of indoor pollutant concentration can be accomplished by increasing supply air velocity, fresh air ratio or cleaning efficiency. However, indoor pollutant concentration is acceptable when supply air velocity exceeds 0.75 m/s. It approaches to a small value (not zero) even in all fresh air operation mode.