Application of indirect tower cooling to telecommunication machine rooms
Zhang Jili, Lu Zhen, Li Zhiyong
Considering that a telecommunication machine room needs cooling all the year round and the major load is sensible heat, designs an indirect tower cooling system combined the cooling tower, plate heat exchanger and air cooler. Presents the main equipments and the determination of their parameters. Taking a machine room in Harbin as an example, calculates the annual cooling load by DeST software, and compares the energy consumption before and after retrofit. As a result, the annual energy saving potential is 40% compared with the original system and the investment payback period is 1.16 years for the indirect tower cooling system. Analyses the energy saving potential of indirect tower cooling system in 31 cities across China, and concludes that the system can save energy 15% to 40% for most cities.