Discussion on some problems in establishing the standard of Commercial or industrial evaporative air-conditioners
Wang Chao, Huang Xiang, Zhang Mingsheng, Huang Hualing
2015.01.05
With an analysis of typical meteorological year data in some representative cities in China’s dry areas and highly humid coastal areas, selects 38 ℃/23 ℃ as the dry bulb temperature and wet bulb temperature of the nominal condition in dry areas and 38 ℃/28 ℃ in coastal areas with high relative humidity. By an analysis obtains the calculation method of the cooling capacity of evaporative air-conditioners, and provides a reference for the determination of the cooling capacity, energy efficiency ratio and testing method.