Influence factors and calculation method of radiant panel cooling capacity
Gao Zhihong, Liu Xiaohua , Zhang Lun, Jiang Yi
2014.12.29
Based on the analysis on existing calculation methods of radiant panel cooling capacity, proposes a method based on indoor equivalent radiant temperature. With a case study, quantitatively analyses the influence of indoor heat sources on cooling capacity of the radiant panel. Suggests the thermal resistance to be used as a main parameter for evaluating the cooling performance of the radiant panel.